AC INPUT TRANSMITTERS
|
|
The JH6010I/6020I series provides an isolated DC output proportional to an AC voltage or current input. Applications range from power monitoring to millivolt-level AC signals from sensors. Input/output isolation is standard to guard against shock hazards in power measurements and against ground loop errors.
Accuracy is better than 0.5% of span. True-rms models maintain accuracy even with nonsinusoidal waveforms. (Standard models are average-responding, calibrated for RMS sine wave response.)
Red-green Quick-Check LEDs give a quick indication of the relative output. Red is brighter at the low end, green at high, while at mid-scale both are approximately equal. Red-only indicates offscale low while green-only indicates offscale high.
Available options include AC or DC power choices and reverse-action Option RT (decreasing output with increasing input).
| Model Number: | Select from the list above. Add suffix -AC for AC power or -DC for DC power. |
| Input Range: | Specify any AC voltage or current range allowed by the "Input Capabilities" spec, below. |
| Output Range: | Specify any DC voltage or current range allowed by the "Output Capabilities" spec, below. |
| Power: | Specify 115Vac, 230Vac, 12Vdc, or 24Vdc. |
| Reverse-Acting Transmitter: | Decreasing output with increasing input. Specify option RT. |
| Loop-Powered Output: | 4/20 mA "current sink" output stage for connection to devices whose inputs provide 24 Vdc loop excitation. Specify Option LPO. |
These transmitters plug into any standard 8-pin circular ("octal") relay socket. JH Technology offers two sockets: DS008 for DIN-rail or surface mounting and ST008 for Snap-Track mounting (see the Accessories page). Pin connections are:
Pin 1: Power (AC or, if DC power option, DC plus).When monitoring the output of a current transformer never use current-input Model JH6020I. Unplugging the module will remove the transformer’s secondary load, resulting in potentially damaging or dangerous voltage spikes (up to several hundred volts).
Instead, use voltage-input Model JH6010I with an appropriate precision external shunt resistor. For 0/5 amps we recommend specifying a 0/250mVac input range with a 0.05 ohm, 0.1% 3 watt external shunt. We offer Part No. R0.05/DS008, a precision shunt resistor assembly preassembled to socket DS008. The socket snaps onto DIN rail or may be surface mounted using screws.
| Voltage Input Capabilties (Model JH6010I): | 50mV Vac minimum span, 250Vac maximum input. Offset ranges are allowed.
(Input Impedance: 200kOhms or greater.) |
| Current Input Capabilities (Model JH6020I): | 1mAac minumum span, 5 Amps ac maximum input. Offset ranges are
allowed.
(Input Resistance: Varies with input range. Contact factory for details. (Warning-see application note above regarding current transformer inputs.) |
| Input Frequency: | 40 to 1,000 Hz for specified accuracy. |
| Voltage Output Capabilities: | 1 volt minumum output span, -10 to +15V absolute limit. Positive offsets are allowed. Maximum output lowad, 10mA (1Kohm at 10V output). |
| Current Output Capabilities: | 1mA minimum output span, 1 to +25mA absolute limit. Positive offsets are allowed, negative outputs are not. Output drive capability, 24V (1,200 ohms max. at 20mA output). |
| Accuracy (factory calibration): | +/-0.02% of span per deg. C, or better. |
| Adjustability: | Zero and span each are adjustable approx. +/-15% of span. |
| Response Time: | Under 200 milliseconds. |
| Isolation: | Power, 1,500Vac rms (2,100V peak). Input/Output, 1,000Vac rms (1,400V peak). |
| Guaranteed Operating Temperature: | -10 to +60 deg. C (14 to 140 deg. F). |
| Temperature Stability: | +/-0.02% of span per deg. C, or better. |
| Power Requirements: | AC, 115 or 230Vrms, 50/60Hz, 2.5V-A. DC, 12 or 24V, 2.5W. |
|
|