Field Mount Transmitters
Temperature
RTD
FDT5400 (Platinum, Copper, Nickel)

FDT5400: 100 ohm Platinum RTD
FDT54x0: reserved for other RTD styles. Contact factory with your requirements.
|
FDT5400 Series RTD Input Transmitters provide an isolated DC output proportional to temperature as measured by a resistance thermometer (RTD). Model FDT5400 specifically designates 100 ohm platinum RTD input: additional model numbers are reserved for other RTD types.
Standard three-wire input circuitry compensates for lead wire resistance: a 4-wire input option is available. Platinum RTDs are linearized to provide true temperature indication. (Other types may or may not be: contact us to discuss your specific requirements.) A low-drift input amplifier helps assure accurate readings under varying ambient conditions.
A rugged NEMA 4X splashproof, corrosion-resistant housing protects the transmitter in outdoor and industrial environments. The circuit boards are urethane coated for protection against condensation and contaminants. FDT5400 Series transmitters include a 3-1/2 digit user-rangeable display to provide local process indication in degrees or other engineering units.
Available options include AC and DC power choices and reverse-acting transmitter (decreasing output with increasing input).
For field mount transmitters without a display, select any plug-in transmitter module plus our ENCL-1 NEMA-4X enclosure. (see Accessories page)
|
Model Number: |
Specify Model FDT5400 for use with 100 ohm platinum RTDs. Other model numbers will be assigned upon request for other RTD types. Contact factory for non-RTD resistance inputs. |
|
Display: |
If not otherwise specified, the display will be calibrated in degrees per your input range. Other calibrations are possible: see "Display Capabilities" specification, below. |
|
Power: |
Add suffix A (for example, FDT5400A) for AC power, D for DC power. Specify 115Vac, 230Vac, 12Vdc or 24Vdc. |
|
RTD Type: |
Model FDT5400: 100 ohm platinum. Others as determined by assigned model number. |
|
Input Range: |
Specify any input range allowed by the "Input Capabilities" spec, below. |
|
Output Range: |
Specify any DC voltage or current range allowed by the "Output Capabilities" spec, below. |
|
4-Wire RTD Input: |
Specify Option 4W. |
|
Reverse-Acting Transmitter (decreasing output with increasing input): |
Change last digit of the model number to 1 (for example, FDT5401A). |
|
Loop-Powered Output: |
4/20mA "current sink" output stage for connection to devices whose inputs provide 24Vdc loop excitation. Change last digit of the model number to 2 (for example, FDT5402A). |
|
Urethane Coating: |
Specify Option U. |
|
Conduit Opening: |
Standard: None. The enclosure has knockouts. Option NPT: Single 1/2 inch NPT fitting (glass-fiber reinforced nylon) at the bottom of the housing. |
Connections are made to 8 terminals within the enclosure:
1: RTD.
2: RTD (same end of RTD as terminal 1). When connecting to 2-wire RTD, jumper terminals 1 and 2. 3: RTD (opposite end)
4: Standard - no connection. Option 4W - 4th wire of RTD (same end as terminal 3).
5: Output plus.
6: Output minus.
7: Power (AC or, if DC power option, DC plus).
8: Power (AC or, if DC power option, DC minus).
|
RTD Type: |
Any RTD from 10 to 2,000 ohms. (Model FDT5400 for 100 ohm platinum, other models FDT54x0 for other types. Contact factory. Specify RTD type, resistance & slope.) |
|
Input Connection: |
3-wire connection is standard. Specify Option 4W for 4-wire RTD. |
|
Input Capabilities: |
Minimum span 10 deg. C (18 deg. F) or 1 ohm, whichever is greater. Any range up to maximum covered by RTD. Offset ranges are allowed. |
|
Voltage Output Capabilities: |
1 volt minimum output span, -10 to +15V absolute limit. Offset ranges are allowed. Maximum output load, 10mA (1Kohm at 10V output). |
|
Current Output Capabilities: |
1mA minimum output span, 0 to +25mA absolute limit. Positive offsets are allowed, negative outputs are not. Output drive capability, 24V (1,200 ohms max. at 20mA output). |
|
Display Capabilities: |
Low end and full scale readings may be anywhere between -1999 and +1999 counts. A fixed decimal point may be added in any position. Minimum span (full scale minus low end) is 10 counts. Reverse-acting display is possible (full scale reading downscale from low end). Display may be re-ranged by user. (Display is normally calibrated in degrees per the input range. If other settings are desired, please specify on your order.) |
|
Endpoint Accuracy (factory calibration): |
+/-0.1% of span or 0.02 ohms, whichever is greater. |
|
Adjustability: |
Zero and span each are adjustable approx. +/-15% of span. |
|
Linearity: |
Platinum RTDs are linearized. Copper is inherently linear. Contact factory for information on others. |
|
Response Time: |
Under 100 milliseconds. |
|
Isolation: |
3-way (Power/Input/Output) 1,500Vac rms (2,100V peak). |
|
Guaranteed Operating Temperature: |
-10 to +60˚C (14 to 140˚F). |
|
Temperature Stability: |
+/-(0.02% of span plus 0.002˚C) per ˚C, or better. |
|
Power Requirements: |
AC, 115 or 230Vrms, 50/60Hz, 2.5V-A. DC, 12 or 24V, 2.5W. |