Field Mount Transmitters
Math(Logic)
FDT5110 (DC 2-Input Add)

FDT5110: (A+B)/2
FDT5120: (A+B+C)/3
FDT5130: (A-B)
|
Also see:
FDT5140/FDT5150 for Multiply/Divide functions
FDT5160/FDT5170 for Square/Square Root functions
FDT5100 Series Add/Subtract Transmitters respond to the sum or difference of 2 or 3 DC inputs and provide a proportional, isolated DC output.
Standard calibration provides low-end output (0%) when all inputs are at 0%. On Models FDT5110 and FDT5120 full-scale output (100%) occurs when all inputs are at 100%. On Model FDT5130, full-scale output occurs when input A is at 100% and input B at 0%. Voltage or current inputs and outputs may be chosen: the input and output ranges need not be the same. Nonstandard calibrations are available, including unequal weighting, dissimilar input ranges and input-to-output offsets. Contact us with your requirements.
A rugged NEMA 4X splashproof, corrosion-resistant housing protects the transmitter in outdoor and industrial environments. The circuit boards are urethane coated for protection against condensation and contaminants. FDT5100 Series transmitters include a 3-1/2 digit user-rangeable display to provide local process indication in engineering units.
Available options include AC and DC power choices and reverse-acting transmitter (decreasing output with increasing input).
For field mount transmitters without a display, select any plug-in transmitter module plus our ENCL-1 NEMA-4X enclosure. (see Accessories page)
|
Model Number: |
Select from the list above according to your input function. |
|
Display: |
Specify display reading at low end and at full scale output, including decimal point if required. See "Display Capabilities" specification, below. Note that reverse-acting display is possible - full scale reading downscale from low end. Display may be re-ranged by user. |
|
Power: |
Add suffix A (for example, FDT5110A) for AC power, D for DC power. Specify 115Vac, 230Vac, 12Vdc or 24Vdc. |
|
Input Range: |
Specify any DC voltage or current range allowed by the "Input Capabilities" spec, below. |
| Output Range: |
Specify any DC voltage or current range allowed by the "Output Capabilities" spec, below. |
|
Reverse-Acting Transmitter (decreasing output with increasing input): |
Change the last digit of the model number to 1 (for example, FDT5111A). |
|
Loop-Powered Output: |
4/20mA "current sink" output stage for connection to devices whose inputs provide 24Vdc loop excitation. Change the last digit of the model number to 2 (for example, FDT5112A). |
|
Urethane Coating: |
Specify Option U. |
|
Conduit Opening: |
Standard: None. The enclosure has knockouts. Option NPT: Single 1/2 inch NPT fitting (glass-fiber reinforced nylon) at the bottom of the housing. |
Connections are made to 8 terminals within the enclosure:
1: Input A (positive).
2: Input common (negative).
3: Input B (positive).
4: Input C (positive - Model FDT5120 only).
5: Output positive.
6: Output negative.
7: Power (AC or, if DC power option, DC plus).
8: Power (AC or, if DC power option, DC minus).
|
Voltage Input Capabilities: |
100mV minimum span, +/-20V maximum input. Offset ranges are allowed. (Input Impedance: 200kohms or greater.) |
|
Current Input Capabilities: |
1mA minimum span, +/-100mA maximum input. Offset ranges are allowed. (Input Resistance: Varies with input range. Contact factory for details. 62 ohms for 4/20mA input.) |
|
Voltage Output Capabilities: |
1 volt minimum output span, -10 to +15V absolute limit. Offset ranges are allowed. Maximum output load, 10mA (1Kohm at 10V output). |
|
Current Output Capabilities: |
1mA minimum output span, 0 to +25mA absolute limit. Positive offsets are allowed, negative outputs are not. Output drive capability, 24V (1,200 ohms max. at 20mA output). |
|
Accuracy (factory calibration): |
+/-0.1% of span. |
|
Adjustability: |
Zero and span each are adjustable approx. +/-15% of span. |
| Linearity: |
+/-0.05% of span or better. |
|
Response Time: |
Under 100 milliseconds. |
|
Isolation: |
3-way (Power/Input/Output) 1,500Vac rms (2,100V peak). (The inputs are not isolated from each other.) |
|
Guaranteed Operating Temperature: |
-10 to +60˚C (14 to 140˚F). |
|
Temperature Stability: |
+/-0.02% of span per ˚C, or better. |
|
Power Requirements: |