FDT5000: DC Voltage Inputs, 1V or Greater
FDT5030: DC 4/20mA Input
FDT5060: DC Current Inputs (except 4/20mA)
FDT5070: DC Millivolt Inputs, less than 1V
|
Also see:
FDT5040: 4/20mA Input with Loop Excitation Supply
FDT5000 Series Field Mount Transmitters provide an isolated DC output proportional to a DC voltage or current input. They are useful for amplifying, reducing, scaling or offsetting signals, for eliminating ground loops and noise problems and for converting currents to voltages or vice-versa. The model numbers listed below reflect a variety of input choices but all share the same basic circuitry, features and specifications.
A rugged NEMA 4X splashproof, corrosion-resistant housing protects the transmitter in outdoor and industrial environments. The circuit boards are urethane coated for protection against condensation and contaminants. FDT5000 Series transmitters include a 3-1/2 digit user-rangeable display to provide local process indication in engineering units.
Model FDT5070 incorporates a low-drift amplifier for millivolt-level inputs. All models use stable, proven circuitry for accurate measurements under varying ambient conditions. Available options include AC and DC power choices and reverse-acting transmitter (decreasing output with increasing input).
For field mount transmitters without a display, select any plug-in transmitter module plus our ENCL-1 NEMA-4X enclosure.(see Accessories page)
|
Model Number: |
Select from the above list according to your input range. Add suffix A (for example, FDT5000A) for AC power, D for DC power. |
| Display: | Specify display reading at low end and at full scale, including decimal point if required. See "Display Capabilities" specification, below. Note that reverse-acting display is possible – full scale reading downscale from low end. Display may be re-ranged by user. |
| Input Range: | Specify any DC voltage or current range allowed by the “Input Capabilities” spec, below. |
| Output Range: | Specify any DC voltage or current range allowed by the “Output Capabilities” spec, below. |
| Power: | Specify 115Vac, 230Vac, 12Vdc or 24Vdc. |
| Reverse-Acting Transmitter(decreasing output with increasing input): | Change last digit of the model number to 1 (for example, FDT5001A). |
| Loop-Powered Output: | 4/20mA “current sink” output stage for connection to devices whose inputs provide 24Vdc loop excitation. Change the last digit of the model number to 2 (for example, FDT5002A). |
| Conduit Opening: | Standard: None. The enclosure has knockouts. Option NPT: Single 1/2 inch NPT fitting (glass-fiber reinforced nylon) at the bottom of the housing. |
Connections are made to 8 terminals within the enclosure:
1: Input plus.
2: Input minus.
3: No connection
4: No connection.
5: Output plus.
6: Output minus.
7: Power (AC or, if DC power option, DC plus).
8: Power (AC or, if DC power option, DC minus).
| Input Capabilities, Model FDT5000: | 1V minimum span, +/-250V maximum input. Offset ranges are allowed. (Input Impedance: 200kohms or greater). |
| Input Range, Model FDT5030: |
4/20mAdc. (62 ohms input resistance. 1.25V drop at full scale.) |
|
Input Capabilities, Model FDT5060: |
1mA minimum span, +/-5 Amps maximum input. Offset ranges are allowed. (Input voltage drop typically 0.1V at full scale.) |
|
Input Capabilities, |
4mV minimum span, 1V maximum span (specify FDT5000 for spans greater than 1V.) Offset ranges are allowed. (Input Impedance: 200kohms or greater.) |
|
Voltage Output Capabilities: |
1 volt minimum output span, -10 to +15V absolute limit. Offset ranges are allowed. Maximum output load, 10mA (1Kohm at 10V output). |
|
Current Output Capabilities: |
1mA minimum output span, 0 to +25mA absolute limit. Positive offsets are allowed, negative outputs are not. Output drive capability, 24V (1,200 ohms max. at 20mA output). |
|
Display Capabilities: |
Low end and full scale readings may be anywhere between -1999 and +1999 counts. A fixed decimal point may be added in any position. Minimum span (full scale minus low end) is 10 counts. Reverse-acting display is possible (full scale reading downscale from low end). Display may be re-ranged by user. |
|
Accuracy(factory calibration): |
+/-0.1% of span or 10 microvolts, whichever is greater. |
|
Adjustability: |
Zero and span each are adjustable approx. +/-15% of span. |
|
Linearity: |
+/-0.05% of span or better. |
|
Response Time: |
Under 100 milliseconds. |
|
Isolation: |
3-way (Power/Input/Output) 1,500Vac rms (2,100V peak). |
|
Guaranteed Operating Temperature: |
-10 to +60oC (14 to 140oF). |
|
Temperature Stability: |
+/-(0.02% of span plus 1.3 microvolts) per oC, or better. |
|
Power Requirements: |
AC, 115 or 230Vrms, 50/60Hz, 2.5V-A. DC, 12 or 24V, 2.5W. |