FDT5600: AC Input, Average Responding
FDT5610: AC Input with True RMS Response
|
Model FDT5600 and FDT5610 AC Input Transmitters provide an isolated DC output proportional to an AC voltage or current input. Input/output isolation is standard to guard against shock hazards in power measurements and against ground loop errors. Inputs ranges may be zero based or may be expanded (for example, 50-150Vac).
A rugged NEMA 4X splashproof, corrosion-resistant housing protects the transmitter in outdoor and industrial environments. The circuit boards are urethane coated for protection against condensation and contaminants. FDT5600 Series transmitters include a 3-1/2 digit user-rangeable display to provide local process indication in engineering units.
Model FDT5600 is average responding, calibrated to provide accurate RMS readings with sine wave inputs. Accuracy is better than 0.5% of span, but will be degraded with nonsinusoidal waveforms such as from SCR/Triac speed and power controllers or pulse-modulated motor drives. For accurate readings with nonsinusoidal waveforms use true-RMS responding Model FT5610.
Available options include AC and DC power choices and reverse-acting transmitter (decreasing output with increasing input).
For field mount transmitters without a display, select any plug-in transmitter module plus our ENCL-1 NEMA-4X enclosure. (see Accessories page)
|
Model Number: |
Specify Model FDT5600 for standard (average responding) or FDT5610 for true-RMS response. |
|
Display: |
Specify display reading at low end and at full scale, including decimal point if required. See "Display Capabilities" specification, below. Note that reverse-acting display is possible - full scale reading downscale from low end. Display may be re-ranged by user. |
|
Power: |
Add suffix A (for example, FDT5600A) for AC power, D for DC power. Specify 115Vac, 230Vac, 12Vdc or 24Vdc. |
|
Input Range: |
Specify any AC voltage or current range allowed by the "Input Capabilities" spec, below. |
|
Output Range: |
Specify any DC voltage or current range allowed by the "Output Capabilities" spec, below. |
|
Reverse-Acting Transmitter (decreasing output with increasing input): |
Change last digit of the model number to 1 (for example, FDT5601A). |
|
Loop-Powered Output: |
4/20mA "current sink" output stage for connection to devices whose inputs provide 24Vdc loop excitation. Change last digit of the model number to 2 (for example, FDT5602A). |
|
Urethane Coating: |
Specify Option U. |
|
Conduit Connection: |
Standard: None. The enclosure has knockouts. Option NPT: Single 1/2 inch NPT fitting (glass-fiber reinforced nylon) at the bottom of the housing. |
Connections are made to 8 terminals within the enclosure:
1: AC signal input.
2: AC signal input.
3: No connection.
4: No connection.
5: Output plus.
6: Output minus.
7: Power (AC or, if DC power option, DC plus).
8: Power (AC or, if DC power option, DC minus).
Model FDT5600 uses average-responding AC/DC converter circuitry calibrated for RMS sine wave response. Pure AC power and other sine wave inputs will be highly accurate. Nonsinusoidal waveforms, however, such as from SCR/Triac power controllers or variable speed drives (pulsed), will produce appreciable errors.
True-rms response, Model FDT5610, gives correct readings regardless of the waveform's shape.
|
Voltage Input Capabilities: |
50mV rms minimum span, 250V maximum input (to 600V rms on special order). Offset ranges are allowed. (Input Impedance: 200kohms or greater.) |
|
Current Input Capabilities: |
1mA rms minimum span, 5 Amps maximum input. Offset ranges are allowed. (Input voltage drop typically 0.1V at full scale. For exact specification for your range, contact factory.) |
|
Input Frequency: |
40 Hz to 1kHz for specified accuracy. |
|
Voltage Output Capabilities: |
1 volt minimum output span, -10 to +15V absolute limit. Offset ranges are allowed. Maximum output load, 10mA (1Kohm at 10V output). |
|
Current Output Capabilities: |
1mA minimum output span, 0 to +25mA absolute limit. Positive offsets are allowed, negative outputs are not. Output drive capability, 24V (1,200 ohms max. at 20mA output). |
|
Display Capabilities: |
Low end and full scale readings may be anywhere between -1999 and +1999 counts. A fixed decimal point may be added in any position. Minimum span (full scale minus low end) is 10 counts. Reverse-acting display is possible (full scale reading downscale from low end). Display may be re-ranged by user. |
|
Accuracy (factory calibration): |
+/-0.5% of span or better. |
|
Adjustability: |
Zero and span each are adjustable approx. +/-15% of span. |
|
Response Time: |
Under 200 milliseconds. |
|
Isolation: |
3-way (Power/Input/Output) 1,500Vac rms (2,100V peak). |
|
Guaranteed Operating Temperature: |
-10 to +60˚C (14 to 140˚F). |
|
Temperature Stability: |
+/-0.02% per ˚C, or better. |
|
Power Requirements: |