DIN RAIL
DC Input
JH5050 (4/20mA isolator)
JH5050 4/20mA CURRENT ISOLATOR
DIN-RAIL MOUNT
.gif)
|
The Model JH5050 4/20mA Current Isolator uses the same high-accuracy circuitry as our other 5000 Series Transmitters. The popularity of this range allows us to reduce costs by premanufacturing and stocking this version. For other ranges and a complete selection of options, please refer to the rest of our 5000 Series product line.
Red-green Quick-Check LEDs give a quick indication of the relative output. Red is brighter at the low end, green at high, while at mid-scale both are approximately equal. Red-only indicates offscale low while green-only indicates offscale high.
AC and DC power choices are available.
| Model Number: | Specify Model JH5050A for AC power, JH5050D for DC power. |
| Input Range: | 4/20mAdc only. |
| Output Range: | 4/20mAdc only. |
| Power: | Specify 115Vac, 230Vac, 12Vdc or 24Vdc. |
Model JH5050 snaps onto 35mm DIN rail. Connections are made to the front-panel terminals. The terminal strip unplugs to facilitate calibrating or replacing the transmitter.
Connections to the 8 terminals (top to bottom) are:
1: Input plus.
2: Input minus.
3: No connection.
4: No connection.
5: Output plus.
6: Output minus.
7: Power (AC or, if DC power option, DC plus).
8: Power (AC or, if DC power option, DC minus).
| Input Range: | 4/20mAdc. (62 ohms input resistance - 1.25V drop at full scale.) |
| Output Range: | 4/20mAdc. Output drive capability, 24V (1,200 ohms max. at 20mA output). |
| Accuracy (factory calibration): | +/-0.1% of span. |
| Adjustability: | Zero and span each are adjustable approx. +/-15% of span. |
| Linearity: | +/-0.05% of span or better. |
| Response Time: | Under 100 milliseconds. |
| Isolation: | 3-way (Power/Input/Output) 1,500Vac rms (2,100V peak). |
| Guaranteed Operating Temperature: | -10 to +60 deg. C (14 to 140 deg. F). |
| Temperature Stability: | +/-0.02% of span per deg. C, or better. |
| Power Requirements: | AC, 115 or 230Vrms, 50/60Hz, 2.5V-A. DC, 12 or 24V, 2.5W. |