Single
Strain Gauge
JH1500 (Bridge Input)

JH1500: Single Trip Alarm
JH1520: Dual Trip Alarm
|
Models JH1500 and JH1520 supply DC excitation to a strain gauge or other resistance bridge, amplify the bridge output and provide relay contact HI/LO trip outputs. Both are fixed-range devices, with input ranges preset per your order.
The alarm trip points are adjustable anywhere within the input range. Deadbands also are fully adjustable, from 0.25% to 100% of span. A slide switch, accessible through the top of the enclosure, selects HI or LO trip operation (on dual alarms, HI/HI, HI/LO or LO/LO). Alarm contacts are rated at 5 amps, 230Vac or 30Vdc. Model JH1520 (dual trip) provides an SPST relay contact for Setpoint #1, SPDT for Setpoint #2. On Model JH1500 (single trip) both sets of contacts respond to the single setpoint.
Red/green LEDs indicate alarm status. A low-drift input amplifier maintains accurate setpoint settings with changing ambient temperature. AC and DC power options are available.
| Model Number: | Select JH1500 single-trip alarm or JH1520 dual-trip alarm. Add suffix –AC for AC power or –DC for DC power. |
| Bridge Excitation: | Specify any voltage between 4 and 12Vdc. Will be factory set to 10V if not specified on your order. User-adjustable. (Note: 40mA maximum load. For 120ohm bridges, specify 4.8V or less.) |
| Input Range: | Specify any input range allowed by the "Input Capabilities" spec, below. Specify either as millivolts per volt, or as millivolts. (Millivolts equals millivolts-per-volt multiplied by the excitation voltage. For example, 0-2.0 mV/V at 10V excitation equals 0-20mV.) |
| Trip Point: | If you would like the trip points to be factory set, please specify the following for each trip point. Specify HI or LO trip, specify the setpoint and specify the amount of deadband required (or specify "minimum deadband"). |
| Relay Action: | Standard is Failsafe - the relay is energized under normal conditions and deenergizes upon alarm or upon loss of power. Thus, loss of power is seen as an alarm condition. Or specify Option R (Reverse Acting) – relay is normally not energized and energizes (pulls in) upon alarm trip. Failsafe is provided if not specified. |
| Power: | Specify 115Vac, 230Vac, 12Vdc or 24Vdc. |
| Urethane Coating: |
Specify Option "U" |
These alarms plug into any standard 11-pin circular ("octal") relay socket. JH Technology offers a socket suitable for DIN-rail or surface mounting (see the Accessories page). Please note – due to limitations on the total number of pins, the relay connections are different from other JH Technology plug-in alarm modules. Pin connections are:
Pin 1: Power (AC or, if DC power option, DC plus).
Pin 2: Setpoint 1 relay moving contact.*
Pin 3: Power (AC or, if DC power option, DC minus).
Pin 4: Input plus (bridge output).
Pin 5: Input minus (bridge output).
Pin 6: Setpoint 1 relay NO contact.*
Pin 7: Bridge excitation plus.
Pin 8: Bridge excitation minus.
Pin 9: Setpoint 2 relay NO contact.*
Pin 10: Setpoint 2 relay moving contact.*
Pin 11: Setpoint 2 relay NC contact.*
| Input Capabilities: | 4mV minimum span (0.4mV/V at 10V excitation). 10V maximum span (1V/V at 10V excitation). Offset ranges are allowed. (Input Impedance: 200kohms.) |
| Excitation Voltage: | Adjustable from 4 to 12Vdc. 40mA maximum load. Factory set to 10Vdc unless otherwise specified. (Note: 120 ohm bridges limited to 4.8V or less. 350 ohm bridges are ok to 12V.) |
| Relay Function, Single Trip Alarm (Model JH1500): | One set of SPST contacts, normally open (open upon loss of power), and one set of SPDT contacts. |
| Relay Function, Dual Alarm (Model JH1520): | Setpoint 1, SPST, normally open (open upon loss of power). Setpoint 2, SPDT relay. |
| Contact Ratings: | 5 Amps resistive, 115/230Vac or 30Vdc. 1/8 HP max inductive load at 115/230Vac. Refer to instructions for contact protection when switching inductive loads. |
| Setpoint Adjustment: | 0% to 100% of range. |
| Deadband Adjustment: | 0.25% to 100% of range. |
| Response Time: | under 100 milliseconds. |
| Isolation: | Input is isolated from power and from relay contacts. 1,500Vac rms (2,100V peak) breakdown. |
| Guaranteed Operating Temperature: | -10 to +60 deg. C (14 to 140 deg. F). |
| Temperature Stability: | +/-(0.02% of span plus 1.3 microvolts) per deg. C, or better. |
| Power Requirements: | AC, 115 or 230Vrms, 50/60 Hz., 2.5V-A. DC, 12 or 24Vdc, 2.5W. |