JH1000: Single Trip Alarm
JH1020: Dual Trip Alarm
|
Models JH1000 and JH1020 DC Input Alarms monitor a DC voltage or current and provide relay contact HI/LO trip outputs. Both are fixed-range devices, with input ranges preset per your order.
The alarm trip points are adjustable anywhere within the input range. Deadbands also are fully adjustable, from 0.25% to 100% of span. A slide switch, accessible through the top of the enclosure, selects HI or LO trip operation (on dual alarms, HI/HI, HI/LO or LO/LO). Red/green LEDs indicate alarm status.
Alarm contacts are rated at 5 amps, 230Vac or 30Vdc. Model JH1000 provides one set of DPDT relay contacts; Model JH1020, two SPDT relays. Both models now include as standard a low-drift input amplifier for millivolt-level signals (formerly an extra-cost option). AC and DC power options are available.
ORDERING INFORMATION
| Model Number: |
Select JH1000 single-trip alarm or JH1020 dual-trip alarm. Add suffix –AC for AC power or –DC for DC power. |
| Input Range: |
Specify any DC voltage or current range allowed by the "Input Capabilities" spec, below. |
| Trip Point: |
If you would like the trip points to be factory set, please specify the following for each trip point. Specify HI or LO trip, specify the setpoint and specify the amount of deadband required (or specify "minimum deadband"). |
| Relay Action: |
Standard is Failsafe - the relay is energized under normal conditions and deenergizes upon alarm or upon loss of power. Thus, loss of power is seen as an alarm condition. Or specify Option R (Reverse Acting) – relay is normally not energized and energizes (pulls in) upon alarm trip. Failsafe is provided if not specified. |
| Power: |
Specify 115Vac, 230Vac, 12Vdc or 24Vdc. |
| Urethane Coating: |
Specify Option "U" |
INSTALLATION AND CONNECTIONS
These alarms plug into any standard 11-pin circular ("octal") relay socket. JH Technology offers a socket suitable for DIN-rail or surface mounting (see the Accessories page). Pin connections are:
Pin 1: Power (AC or, if DC power option, DC plus).
Pin 2: No connection.
Pin 3: Power (AC or, if DC power option, DC minus).
Pin 4: Input plus.
Pin 5: Input minus.
Pin 6: Setpoint 1 relay NO contact.*
Pin 7: Setpoint 1 relay moving contact.*
Pin 8: Setpoint 1 relay NC contact.*
Pin 9: Setpoint 2 relay NO contact.*
Pin 10: Setpoint 2 relay moving contact.*
Pin 11: Setpoint 2 relay NC contact.*
DETAILED SPECIFICATIONS
| Voltage Input Capabilities: | 4mV minimum span, +/-250V maximum input. Offset ranges are allowed. (Input Impedance: 200Kohms or greater.) |
| Current Input Capabilities: |
1mA minimum span, +/-5 Amps maximum input. Offset ranges are allowed. (Input Resistance: Varies with input range. Contact factory for details. 62 ohms for 4/20mA input.) |
| Relay Contacts: |
Single Alarm, one DPDT relay. Dual Alarm, two SPDT relays. Contacts rated 5 Amps resistive, 115/230Vac or 30Vdc. 1/8 HP max inductive load at 115/230Vac. Refer to instructions for contact protection when switching inductive loads. |
| Setpoint Adjustment: |
0% to 100% of range. |
| Deadband Adjustment: |
0.25% to 100% of range. |
| Response Time: |
under 100 milliseconds. |
| Isolation: |
Input is isolated from power and from relay contacts. 1,500Vac rms (2,100V peak) breakdown. |
| Guaranteed Operating Temperature: |
-10 to +60 deg. C (14 to 140 deg. F). |
| Temperature Stability: |
+/-(0.02% of span plus 1.3 microvolts) per deg. C, or better. |
| Power Requirements: |
AC, 115 or 230Vrms, 50/60 Hz., 2.5V-A. DC, 12 or 24Vdc, 2.5W. |