FT5400 FIELD MOUNT TRANSMITTER RTD INPUT

FT5400: 100 ohm Platinum RTD, Linearized
FDT5400: 100 ohm Platinum RTD,
Linearized, with optional display Model numbers
FT/FDT54x0: reserved for other
RTD styles. Contact factory with your requirements.
- NEMA 4X Splashproof Enclosure
- Optional 3-1/2 Digit Display
- Available
for all RTD Types
- Linearizes Platinum RTDs
- 3-Wire Lead Compensation
Standard
- Urethane-Coated Circuit Boards
- AC or DC Power Options
|
FT5400/FTD5400
PDF
DATA SHEET |
FT5400 Series RTD Input Transmitters provide an isolated DC output
proportional to temperature as measured by a resistance thermometer (RTD). Model
FT5400 specifically designates 100 ohm platinum RTD input: additional model
numbers are reserved for other RTD types.
Standard three-wire input circuitry compensates for lead wire resistance: a
4-wire input option is available. Platinum RTDs are linearized to provide true
temperature indication. (Other types may or may not be: contact us to discuss
your specific requirements.) A low-drift input amplifier helps assure accurate
readings under varying ambient conditions.
A rugged NEMA 4X splashproof, corrosion-resistant housing protects the
transmitter in outdoor and industrial environments. The circuit boards are
urethane coated for protection against condensation and contaminants. FDT5400
Series transmitters include a 3-1/2 digit user-rangeable display to provide
local process indication in degrees or other engineering units.
Available options include AC and DC power choices and reverse-acting
transmitter (decreasing output with increasing input).
ORDERING INFORMATION
|
Model Number:
|
Specify Model FT5400 for use with 100 ohm platinum RTDs. Other
model numbers will be assigned upon request for other RTD types. Contact factory
for non-RTD resistance inputs.
|
|
Optional Display:
|
Change FT to FDT (FDT5400). If not otherwise specified, the
display will be calibrated in degrees per your input range. Other calibrations
are possible: see "Display Capabilities" specification, below.
|
|
Power:
|
Add suffix A (for example, FT5400A) for AC power, D for DC power.
Specify 115Vac, 230Vac, 12Vdc or 24Vdc.
|
|
RTD Type:
|
Model FT/FDT5400: 100 ohm platinum. Others as determined by
assigned model number.
|
|
Input Range:
|
Specify any input range allowed by the "Input
Capabilities" spec, below.
|
|
Output Range:
|
Specify any DC voltage or current range allowed by the
"Output Capabilities" spec, below.
|
|
4-Wire RTD:
|
Specify Option 4W.
|
|
Reverse-Acting Transmitter (decreasing output with increasing input):
|
Change
last digit of the model number to 1 (for example, FT5401A).
|
|
Loop-Powered Output:
|
4/20mA "current sink" output stage for
connection to devices whose inputs provide 24Vdc loop excitation. Change last
digit of the model number to 2 (for example, FDT5402A). |
|
Urethane Coating:
|
Specify Option U.
|
|
Conduit Connection:
|
Standard: A single 1/2 inch NPT conduit fitting
(glass-fiber reinforced nylon) is provided at the bottom of the housing. Other
options are possible, including no fitting at all. Contact factory
|
ELECTRICAL CONNECTIONS
Connections are made to 8 terminals within the enclosure:
1: RTD.
2: RTD (same end of RTD as terminal 1). When connecting to 2-wire RTD,
jumper terminals 1 and 2. 3: RTD (opposite end)
4: Standard - no connection.
Option 4W - 4th wire of RTD (same end as terminal 3).
5: Output plus.
6: Output
minus.
7: Power (AC or, if DC power option, DC plus).
8: Power (AC or, if DC
power option, DC minus).
DETAILED SPECIFICATIONS
|
RTD Type:
|
Any RTD from 10 to 2,000 ohms. (Model FT/FDT5400 for 100 ohm
platinum, other models FT/FDT54x0 for other types. Contact factory. Specify RTD
type, resistance & slope.)
|
|
Input Connection:
|
3-wire connection is standard. Specify Option 4W for 4-wire
RTD.
|
|
Input Capabilities:
|
Minimum span 10 deg. C (18 deg. F) or 1 ohm, whichever is
greater. Any range up to maximum covered by RTD. Offset ranges are allowed.
|
|
Voltage Output Capabilities:
|
1 volt minimum output span, -10 to +15V absolute
limit. Offset ranges are allowed. Maximum output load, 10mA (1Kohm at 10V
output).
|
|
Current Output Capabilities:
|
1mA minimum output span, 0 to +25mA absolute
limit. Positive offsets are allowed, negative outputs are not. Output drive
capability, 24V (1,200 ohms max. at 20mA output).
|
|
Display Capabilities:
|
Low end and full scale readings may be anywhere between
-1999 and +1999 counts. A fixed decimal point may be added in any position.
Minimum span (full scale minus low end) is 10 counts. Reverse-acting display is
possible (full scale reading downscale from low end). Display may be re-ranged
by user. (Display is normally calibrated in degrees per the input range. If
other settings are desired, please specify on your order.)
|
|
Endpoint Accuracy (factory calibration):
|
+/-0.1% of span or 0.02 ohms,
whichever is greater.
|
|
Adjustability:
|
Zero and span each are adjustable approx. +/-15% of span.
|
|
Linearity:
|
Platinum RTDs are linearized. Copper is inherently linear. Contact
factory for information on others.
|
|
Response Time:
|
Under 100 milliseconds.
|
|
Isolation:
|
3-way (Power/Input/Output) 1,500Vac rms (2,100V peak).
|
|
Guaranteed Operating Temperature:
|
-10 to +60OC (14 to 140OF).
|
|
Temperature Stability:
|
+/-(0.02% of span plus 0.002OC) per OC, or better.
|
|
Power Requirements:
|