FT5100 SERIES FIELD MOUNT TRANSMITTERS ADD-SUBTRACT DC INPUTS

FT5110: (A+B)/2
FT5120: (A+B+C)/3
FT5130: (A-B)
- NEMA 4X Splashproof Enclosure
- Optional 3-1/2 Digit Display
- Voltage
or Current Inputs and Outputs
- Nonstandard Ranges Available
- Input/Output
Isolation Standard
- Urethane-Coated Circuit Boards
- AC or DC Power Options
|
FT5110/FT5120/FT5130
PDF
DATA SHEET |
Also see:
FT5140/FT5150 for Multiply/Divide functions
FT5100 Series Add/Subtract Transmitters respond to the sum or difference of 2
or 3 DC inputs and provide a proportional, isolated DC output.
Standard calibration provides low-end output (0%) when all inputs are at 0%.
On Models FT5110 and FT5120 full-scale output (100%) occurs when all inputs are
at 100%. On Model FT5130, full-scale output occurs when input A is at 100% and
input B at 0%. Voltage or current inputs and outputs may be chosen: the input
and output ranges need not be the same. Nonstandard calibrations are available,
including unequal weighting, dissimilar input ranges and input-to-output
offsets. Contact us with your requirements.
A rugged NEMA 4X splashproof, corrosion-resistant housing protects the
transmitter in outdoor and industrial environments. The circuit boards are
urethane coated for protection against condensation and contaminants. FDT5100
Series transmitters include a 3-1/2 digit user-rangeable display to provide
local process indication in engineering units.
Available options include AC and DC power choices and reverse-acting
transmitter (decreasing output with increasing input).
ORDERING INFORMATION
|
Model Number:
|
Select from the list above according to your input function.
|
|
Optional Display:
|
Change FT to FDT (for example, FDT5110A). Specify display
reading at low end and at full scale output, including decimal point if
required. See "Display Capabilities" specification, below. Note that
reverse-acting display is possible - full scale reading downscale from low end.
Display may be re-ranged by user.
|
|
Power:
|
Add suffix A (for example, FT5110A) for AC power, D for DC power.
Specify 115Vac, 230Vac, 12Vdc or 24Vdc.
|
|
Input Range:
|
Specify any DC voltage or current range allowed by the
"Input Capabilities" spec, below.
|
| Output Range: |
Specify any DC voltage or current range allowed by the
"Output Capabilities" spec, below.
|
|
Reverse-Acting Transmitter (decreasing output with increasing input):
|
Change
the last digit of the model number to 1 (for example, FT5111A).
|
|
Loop-Powered Output:
|
4/20mA "current sink" output stage for
connection to devices whose inputs provide 24Vdc loop excitation. Change the
last digit of the model number to 2 (for example, FDT5112A).
|
|
Urethane Coating:
|
Specify Option U.
|
|
Conduit Connection:
|
Standard: A single 1/2 inch NPT conduit fitting
(glass-fiber reinforced nylon) is provided at the bottom of the housing. Other
options are possible, including no fitting at all. Contact factory. |
ELECTRICAL CONNECTIONS
Connections are made to 8 terminals within the enclosure:
1: Input A (positive).
2: Input common (negative).
3: Input B (positive).
4:
Input C (positive - Model FT5120 only).
5: Output positive.
6: Output negative.
7: Power (AC or, if DC power option, DC plus).
8: Power (AC or, if DC power
option, DC minus).
DETAILED SPECIFICATIONS
|
Voltage Input Capabilities:
|
100mV minimum span, +/-20V maximum input. Offset
ranges are allowed. (Input Impedance: 200kohms or greater.)
|
|
Current Input Capabilities:
|
1mA minimum span, +/-100mA maximum input. Offset
ranges are allowed. (Input Resistance: Varies with input range. Contact factory
for details. 62 ohms for 4/20mA input.)
|
|
Voltage Output Capabilities:
|
1 volt minimum output span, -10 to +15V absolute
limit. Offset ranges are allowed. Maximum output load, 10mA (1Kohm at 10V
output).
|
|
Current Output Capabilities:
|
1mA minimum output span, 0 to +25mA absolute
limit. Positive offsets are allowed, negative outputs are not. Output drive
capability, 24V (1,200 ohms max. at 20mA output).
|
|
Accuracy (factory calibration):
|
+/-0.1% of span.
|
|
Adjustability:
|
Zero and span each are adjustable approx. +/-15% of span.
|
| Linearity: |
+/-0.05% of span or better.
|
|
Response Time:
|
Under 100 milliseconds.
|
|
Isolation:
|
3-way (Power/Input/Output) 1,500Vac rms (2,100V peak). (The inputs
are not isolated from each other.)
|
|
Guaranteed Operating Temperature:
|
-10 to +60oC (14 to 140oF).
|
|
Temperature Stability:
|
+/-0.02% of span per oC, or better.
|
|
Power Requirements:
|
AC, 115 or 230Vrms, 50/60Hz, 2.5V-A. DC, 12 or 24V, 2.5W.
|
|