FT5040 FIELD MOUNT TRANSMITTER 4/20mA INPUT W/LOOP EXCITATION SUPPLY

- NEMA 4X Splashproof Enclosure
- Optional 3-1/2 Digit Display
- Provides
24Vdc Power to Input Loop
- 4/20mA Input Standard, Others Available
- Input/Output Isolated
- Urethane-Coated Circuit Boards
- AC or DC Power
Options
|
FT5040
PDF
DATA SHEET |
The Model FT5040 DIN-Rail Transmitter provides an isolated DC voltage or
current output proportional to a 4/20mAdc input. Designed to isolate and convert
signals from 2-wire (loop-powered) transmitters, it includes a regulated 24Vdc
input loop supply.
A rugged NEMA 4X splashproof, corrosion-resistant housing protects the
transmitter in outdoor and industrial environments. The circuit boards are
urethane coated for protection against condensation and contaminants. Model
FDT5040 includes a 3-1/2 digit user-rangeable display to provide local process
indication in engineering units.
Other input ranges are possible. For example, the FT/FDT5040 may be used with
DC-powered "3-wire" sensors and transmitters whose supply currents do
not exceed 25mA. Input/output isolation overcomes the ground loop problems
sometimes encountered with nonisolated DC-powered transmitters.
Available options include AC and DC power choices and reverse-acting
transmitter (decreasing output with increasing input).
ORDERING INFORMATION
| Model Numbers: |
FT5040: Transmitter only. FDT5040: Transmitter with display.
|
| Power: |
Add suffix A (Model FT/FDT5040A) for AC power, D for DC power. Specify
115Vac, 230Vac, 12Vdc or 24Vdc.
|
| Input Range: |
Select 4/20mA for use with 2-wire inputs, or any other range
allowed by the "Input Capabilities" spec, below.
|
| Output Range: |
Specify any DC voltage or current range allowed by the
"Output Capabilities" spec, below.
|
| Display Range (optional): |
Specify display reading at low end and at full
scale, including decimal point if required. See "Display Capabilities"
specification, below. Note that reverse-acting display is possible - full scale
reading downscale from low end. Display may be re-ranged by user.
|
| Reverse-Acting Transmitter (decreasing output with increasing
input): |
Change
model number to FT/FDT5041(A or D).
|
| Loop-Powered Output: |
4/20mA "current sink" output stage for
connection to devices whose inputs provide 24Vdc loop excitation. Change model
number to FT/FDT5042(A or D).
|
| Conduit Connection: |
Standard: A single 1/2 inch NPT conduit fitting
(glass-fiber reinforced nylon) is provided at the bottom of the housing. Other
options are possible, including no fitting at all. Contact factory
|
ELECTRICAL CONNECTIONS
Connections are made to 8 terminals within the enclosure:
1: Input plus.
2: Input minus.
3: +24Vdc loop excitation.
4: No connection.
5: Output plus.
6: Output minus.
7: Power (AC or, if DC power option, DC plus).
8: Power (AC or, if DC power option, DC minus).
DETAILED SPECIFICATIONS
| Voltage Input Capabilities: |
50mV minimum span, +/-20V maximum input. Offset
ranges are allowed. (Input Impedance: 200kohms or greater.)
|
| Current Input Capabilities: |
1mA minimum span, 0/25mA maximum input. Specify
4/20mA when used with a 2-wire transmitter. Offset ranges are allowed. (Input
resistance varies with input range. Contact factory for details. 62 ohms for
4/20mA input.)
|
| Input Excitation: |
24Vdc regulated. 25mA max. current.
|
| Voltage Output Capabilities: |
1 volt minimum output span, -10 to +15V absolute
limit. Offset ranges are allowed. Maximum output load, 10mA (1Kohm at 10V
output).
|
| Current Output Capabilities: |
1mA minimum output span, 0 to +25mA absolute
limit. Positive offsets are allowed, negative outputs are not. Output drive
capability, 24V (1,200 ohms max. at 20mA output).
|
| Display Capabilities: |
Low end and full scale readings may be anywhere between
-1999 and +1999 counts. A fixed decimal point may be added in any position.
Minimum span (full scale minus low end) is 10 counts. Reverse-acting display is
possible (full scale reading downscale from low end). Display may be re-ranged
by user.
|
| Accuracy (factory calibration): |
+/-0.1% of span.
|
| Adjustability: |
Zero and span each are adjustable approx. +/-15% of span.
|
| Linearity: |
+/-0.05% of span or better.
|
| Response Time: |
Under 100 milliseconds.
|
| Isolation: |
3-way (Power/Input/Output) 1,500Vac rms (2,100V peak).
|
| Guaranteed Operating Temperature: |
-10 to +60oC (14 to 140oF).
|
| Temperature Stability: |
+/-0.02% of span per oC, or better.
|
| Power Requirements: |
AC, 115 or 230Vrms, 50/60Hz, 2.5V-A. DC, 12 or 24V, 2.5W.
|
|