JH5600/5610 AC INPUT TRANSMITTERS
DIN-RAIL MOUNT, FIXED RANGE

JH5600: AC Input Transmitter
JH5610: AC Input Transmitter with True RMS Response
- Translates AC Voltages or Currents to DC
- Inputs from 50mV to 250Vrms, 1mA to 5 Amps RMS
- True-RMS Response Option Available
- Quick-Check Red/Green Output LEDs
- Unpluggable Terminal Strip
- AC or DC Power Options
|
JH5600/JH5610
PDF
DATA SHEET |
Model JH5600 and JH5610 AC Input Transmitters provide an isolated DC output
proportional to an AC voltage or current input.
Model JH5600 is average responding, calibrated to provide accurate RMS
readings with sine wave inputs. Accuracy will be degraded with nonsinusoidal
waveforms such as from SCR/Triac speed and power controllers or pulse-modulated
motor drives. For accurate readings with nonsinusoidal waveforms use true-RMS
responding Model JH5610.
Red-green Quick-Check LEDs give a quick indication of the relative output.
Red is brighter at the low end, green at high, while at mid-scale both are
approximately equal. Red-only indicates offscale low while green-only indicates
offscale high.
Available options include AC and DC power choices and reverse-acting
transmitter (decreasing output with increasing input).
ORDERING INFORMATION
| Model Number: |
Specify Model JH5600 for standard
(average responding) or JH5610 for true-RMS response. Add suffix A (for
example, JH5600A) for AC power, D for DC power. |
| Input Range: |
Specify any AC voltage or current
range allowed by the "Input Capabilities" spec, below. |
| Output Range: |
Specify any DC voltage or current
range allowed by the "Output Capabilities" spec, below. |
| Power: |
Specify 115Vac, 230Vac, 12Vdc or
24Vdc. |
| Reverse-Acting Transmitter
(decreasing output with increasing input): |
Change last digit of the model number
to 1 (for example, JH5601A). |
| Loop-Powered Output: |
4/20mA "current sink" output stage
for connection to devices whose inputs provide 24Vdc loop excitation.
Change last digit of the model number to 2 (for example, JH5602A). |
| Urethane Coating: |
Specify Option U. |
JH5600 Series transmitters snap onto 35mm DIN rail. Connections are made to
the front-panel terminals. The terminal strip unplugs to facilitate calibrating
or replacing the transmitter.
Connections to the 8 terminals (top to bottom) are:
1: AC input.
2: AC input.
3: No connection.
4: No connection.
5: Output plus.
6: Output minus.
7: Power (AC or, if DC power option, DC
plus).
8: Power (AC or, if DC power option, DC
minus).
DETAILED SPECIFICATIONS
| Voltage Input Capabilities: |
50mV rms minimum span, +/-250V
maximum input (to 600V rms on special order). Offset ranges are allowed.
(Input Impedance: 200kohms or greater.) |
| Current Input Capabilities: |
1mA minimum span, +/-5 Amps maximum
input. Offset ranges are allowed. (Input voltage drop typically 0.1V at
full scale.) |
| Input Frequency: |
40 Hz to 1kHz. For rated accuracy,
Model JH5600 requires a sine wave input. Model 5610 (true RMS) remains
accurate with any waveform. |
| Voltage Output Capabilities: |
1 volt minimum output span, -10 to
+15V absolute limit. Offset ranges are allowed. Maximum output load,
10mA (1Kohm at 10V output). |
| Current Output Capabilities: |
1mA minimum output span, 0 to +25mA
absolute limit. Positive offsets are allowed, negative outputs are not.
Output drive capability, 24V (1,200 ohms max. at 20mA output). |
| Accuracy (factory calibration): |
+/-0.5% of span or better. |
| Adjustability: |
Zero and span each are adjustable
approx. +/-15% of span. |
| Linearity: |
+/-0.1% of span or better. |
| Response Time: |
Under 200 milliseconds. |
| Isolation: |
3-way (Power/Input/Output) 1,500Vac
rms (2,100V peak). |
| Guaranteed Operating Temperature: |
-10 to +60 deg. C (14 to 140 deg. F). |
| Temperature Stability: |
+/-0.02% per deg. C, or better. |
| Power Requirements: |
AC, 115 or 230Vrms, 50/60Hz, 2.5V-A.
DC, 12 or 24V, 2.5W. |
|