JH5100 SERIES SQUARE/SQUARE ROOT TRANSMITTERS
DIN-RAIL MOUNT, FIXED RANGE

JH5160: A²
JH5170: √A
- Takes the square or square root of a DC signal
- Input and Output ranges need not be the same
- Input/Output Isolation Standard
- Quick-Check Red/Green Output LEDs
- High Speed "Option HS" Available
- DIN-Rail Mount, 1 Inch Wide
- Unpluggable Terminal Strip
- AC or DC Power Options
|
JH5160/JH5170
PDF
DATA SHEET |
JH5170
PDF
MANUAL |
Also see:
JH5110/ JH5120/JH5130
for Add/Subtract functions
JH5140/ JH5150 for Multiply/Divide functions
JH5160/JH5170 Square/Square Root Transmitters provide DC outputs proportional to
the square or square root of the input. The square root function is most
commonly used to linearize differential pressure flow signals.
The input and output ranges need not be the same; for example, the input
could be 0/10Vdc while the output could be 4/20mA. These are fixed range
devices, precisely calibrated to your specified ranges at the factory.
Red-green Quick-Check LEDs give a quick indication of the relative output.
Red is brighter at the low end, green at high, while at mid-scale both are
approximately equal. Red-only indicates offscale low while green-only indicates
offscale high.
Standard transmitters include filtering to smooth measurements and minimize
noise pickup. When fast response is needed, Option HS speeds the response time
to approximately 1 millisecond. Other response speeds are available on special
order.
Input/output isolation is standard. Available options include AC or DC power
choices and reverse-action transmitter (decreasing output with increasing
input).
ORDERING INFORMATION
| Model Number: |
Select from the list above according
to your input function. Add suffix A (for example, JH5160A) for AC
power, D for DC power. |
| Input Range: |
Specify any DC voltage or current
range allowed by the "Input Capabilities" spec, below. |
| Output Range: |
Specify any DC voltage or current
range allowed by the "Output Capabilities" spec, below. |
| Power: |
Specify 115Vac, 230Vac, 12Vdc or
24Vdc. |
| Reverse-Acting Transmitter (decreasing
output with increasing input): |
Change the last digit of the model number to
1 (for example, JH5161A). |
| Loop-Powered Output: |
4/20mA "current sink" output stage
for connection to devices whose inputs provide 24Vdc loop excitation.
Change the last digit of the model number to 2 (for example, JH5162A). |
|
High Speed Response: |
Approximately 1 msec (See Specifications). Specify Option HS.
|
| Urethane Coating: |
Specify Option U. |
INSTALLATION AND CONNECTIONS
JH5100 Series transmitters snap onto 35mm DIN rail. Connections are made to
the front-panel terminals. The terminal strip unplugs to facilitate calibrating
or replacing the transmitter.
Connections to the 8 terminals (top to bottom) are:
1: Input plus
2: Input minus
3: not connected
4: not connected
5: Output plus
6: Output minus
7: Power (AC or, if DC power option, DC plus).
8: Power (AC or, if DC power option, DC minus).
DETAILED SPECIFICATIONS
|
Voltage Input Capabilities: |
100mV minimum span, +/-20V maximum input.
Offset ranges are allowed. (Input Impedance: 200kohms or greater.)
|
|
Current Input Capabilities: |
1mA minimum span, +/-100mA maximum input.
Offset ranges are allowed. (Input Resistance: Varies with input range. Contact factory for details. 62 ohms for 4/20mA input).
|
|
Voltage Output Capabilities: |
1 volt minimum output span, -10 to +15V absolute limit. Offset ranges
are allowed. Maximum output load, 10mA (1Kohm at 10V output).
|
|
Current Output Capabilities: |
1mA minimum output span, 0 to +25mA absolute
limit. Positive offsets are allowed, negative outputs are not. Output drive
capability, 24V (1,200 ohms max. at 20mA output).
|
| Accuracy (factory calibration): |
+/-0.2% of span or better. (For square root function Model JH5170 the input
must be greater than 20% of span for rated accuracy).
|
|
Adjustability: |
Zero and span each are adjustable approx. +/-15% of span.
|
|
Response Time: |
Standard: Under 100 milliseconds. Option HS: Approximately 95% complete in 1
msec. Frequency response 3dB down at approx. 600Hz.
|
|
Isolation: |
3-way (Power/Input/Output) 1,500Vac rms (2,100V peak).
|
|
Operating Temperature: |
-10 to +60˚C (14 to 140˚F).
|
|
Temperature Stability: |
+/-0.02% of span per ˚C, or better.
|
|
Power Requirements: |
AC, 115 or 230Vrms, 50/60Hz, 2.5W. DC, 12 or 24V,
2.5W.
|
|