RTD INPUT PLUG-IN ALARM MODULES

JH1400: Single Trip Alarm
JH1420: Dual Trip Alarm
- 3-Wire Lead Resistance Compensation
- Platinum, Nickel and other RTDs
- Switch-Selectable HI/LO Trip Function
- Adjustable Deadband Standard
- Uses Standard 11-Pin Socket
- AC or DC Power Options
|
JH1400/JH1420
PDF
DATA SHEET |
Models JH1400 and JH1420 RTD Input Alarms monitor temperature as measured by a resistance
thermometer (RTD) and provide relay contact HI/LO trip outputs. Both are fixed-range devices, with input
ranges preset per your order. These alarms also may be ordered with setups to monitor resistances other than
RTDs
The alarm trip points are adjustable anywhere within the input range. Deadbands also are
fully adjustable, from 0.25% to 100% of span. A slide switch, accessible through the top of the enclosure,
selects HI or LO trip operation (on dual alarms, HI/HI, HI/LO or LO/LO). Red/green LEDs indicate alarm
status.
Alarm contacts are rated at 5 amps, 230Vac or 30Vdc. Model JH1400 provides one set of DPDT
relay contacts; Model JH1420, two SPDT relays. Three-wire input circuitry compensates for lead wire
resistance. AC and DC power options are available.
ORDERING INFORMATION
| Model Number: |
Select JH1400 single-trip alarm or JH1420 dual-trip alarm.
Add suffix –AC for AC power or –DC for DC power. |
| RTD: |
Specify any standard RTD type between 10 and 2,000 ohms, or provide
details for nonstandard RTD or resistance input. |
| Input Range: |
Specify any range allowed by the "Input Capabilities"
spec, below. |
| Trip Point: |
If you would like the trip points to be factory set, please specify
the following for each trip point. Specify HI or LO trip, specify the setpoint and specify the amount of
deadband required (or specify "minimum deadband"). |
| Relay Action: |
Standard is Failsafe - the relay is energized under normal
conditions and deenergizes upon alarm or upon loss of power. Thus, loss of power is seen as an alarm
condition. Or specify Option R (Reverse Acting) – relay is normally not energized and energizes
(pulls in) upon alarm trip. Failsafe is provided if not specified. |
| Power: |
Specify 115Vac, 230Vac, 12Vdc or 24Vdc. |
INSTALLATION AND CONNECTIONS
These alarms plug into any standard 11-pin circular ("octal") relay socket. JH
Technology offers two sockets: DS011 for DIN-rail or surface mounting and ST011 for Snap-Track mounting (see
the Accessories page). Pin connections are:
Pin 1: Power (AC or, if DC power option, DC plus).
Pin 2: RTD.
Pin 3: Power (AC or, if DC power option, DC minus).
Pin 4: RTD (opposite end from Pins 2 and 5).
Pin 5: RTD compensation (same end of RTD as pin 2.
Pin 6: Setpoint 1 relay NO contact.*
Pin 7: Setpoint 1 relay moving contact.*
Pin 8: Setpoint 1 relay NC contact.*
Pin 9: Setpoint 2 relay NO contact.*
Pin 10: Setpoint 2 relay moving contact.*
Pin 11: Setpoint 2 relay NC contact.*
- Notes: NO (normally open) and NC (normally closed) refer to the relay state when no power
is applied. For Failsafe operation the NO contacts are closed under nonalarm conditions. The NC contacts
close upon alarm and upon loss of power. The terms Setpoint 1 and Setpoint 2 refer to dual-trip alarms. For
single-trip alarms, both sets of contacts respond to the one trip point.
DETAILED SPECIFICATIONS
| RTD Type: |
Any RTD from 10 to 2,000 ohms. 3-wire connection (can also be
connected as 2-wire). Specify RTD type, slope and resistance, or provide details for nonstandard RTD. Contact
factory for other types of resistance inputs. |
| Input Capabilities: |
Minimum span 10 deg C (18 deg F) or 1 ohm, whichever is greater. Any
range up to maximum covered by RTD. Offset ranges are allowed. |
| Relay Contacts: |
Single Alarm, one DPDT relay. Dual Alarm, two SPDT relays. Contacts
rated 5 Amps resistive, 115/230Vac or 30Vdc. 1/8 HP max inductive load at 115/230Vac. Refer to instructions
for contact protection when switching inductive loads. |
| Setpoint Adjustment: |
0% to 100% of range. |
| Deadband Adjustment: |
0.25% to 100% of range. |
| Response Time: |
under 100 milliseconds. |
| Isolation: |
Input is isolated from power and from relay contacts. 1,500Vac rms
(2,100V peak) breakdown. |
| Guaranteed Operating Temperature: |
-10 to +60 deg. C (14 to 140 deg. F). |
| Temperature Stability: |
+/-0.02% of span per deg. C, or better. |
| Power Requirements: |
AC, 115 or 230Vrms, 50/60 Hz., 2.5V-A. DC, 12 or 24Vdc, 2.5W. |
|