THERMOCOUPLE INPUT PLUG-IN ALARM MODULES

JH1200: Single Trip Alarm
JH1220: Dual Trip Alarm
- Available for All Thermocouple Types
- Low-Drift Input Amplifier
- Jumper-Selectable Upscale/Downscale Burnout
- Switch-Selectable HI/LO Trip Function
- Adjustable Deadband Standard
- AC or DC Power Options
|
JH1200/JH1220
PDF
DATA SHEET |
Models JH1200 and JH1220 Thermocouple Alarms monitor temperature as measured by a
thermocouple and provide relay contact HI/LO trip outputs. Both are fixed-range devices, with input ranges
preset per your order.
The alarm trip points are adjustable anywhere within the input range. Deadbands also are
fully adjustable, from 0.25% to 100% of span. A slide switch, accessible through the top of the enclosure,
selects HI or LO trip operation (on dual alarms, HI/HI, HI/LO or LO/LO). Red/green LEDs indicate alarm
status. Model JH1200 provides one set of DPDT relay contacts; Model JH1220, two SPDT relays. Alarm contacts
are rated at 5 amps, 230Vac or 30Vdc.
A low-drift input amplifier plus automatic cold-junction compensation maintain accurate
setpoint settings with changing ambient temperatures. An internal jumper allows
HI or LO trip indication upon thermocouple burnout. AC and DC power options are available.
ORDERING INFORMATION
| Model Number: |
Select JH1200 single-trip alarm or JH1220 dual-trip alarm.
Add suffix –AC for AC power or –DC for DC power. |
| Thermocouple Type: |
Specify type J, K, T, E, R, S, B or N, or contact factory for
others. |
| Input Range: |
Specify any input range corresponding to 4mV or higher span.
(4mV equals 100 deg. C for type K thermocouples.). |
| T/C Burnout Indication: |
Specify upscale (high) or downscale (low) burnout indication.
Will be set for upscale if not specified on your order. |
| Trip Point: |
If you would like the trip points to be factory set, please
specify the following for each trip point. Specify HI or LO trip, specify the setpoint and specify the amount
of deadband required (or specify "minimum deadband"). |
| Relay Action: |
Standard is Failsafe - the relay is energized under
normal conditions and deenergizes upon alarm or upon loss of power. Thus, loss of power is seen as an alarm
condition. Or specify Option R (Reverse Acting) – relay is normally not energized and energizes
(pulls in) upon alarm trip. Failsafe is provided if not specified. |
| Power: |
Specify 115Vac, 230Vac, 12Vdc or 24Vdc. |
INSTALLATION AND CONNECTIONS
These alarms plug into any standard 11-pin circular ("octal") relay socket. JH
Technology offers two sockets: DS011 for DIN-rail or surface mounting and ST011 for Snap-Track mounting (see
the Accessories page).
The thermocouple connects to a small terminal block (which also contains cold junction
compensation) on the side of the module. The remaining pin connections are:
Pin 1: Power (AC or, if DC power option, DC plus).
Pin 2: No connection.
Pin 3: Power (AC or, if DC power option, DC minus).
Pin 4: No connection.
Pin 5: No connection.
Pin 6: Setpoint 1 relay NO contact.*
Pin 7: Setpoint 1 relay moving contact.*
Pin 8: Setpoint 1 relay NC contact.*
Pin 9: Setpoint 2 relay NO contact.*
Pin 10: Setpoint 2 relay moving contact.*
Pin 11: Setpoint 2 relay NC contact.*
- Notes: NO (normally open) and NC (normally closed) refer to the relay state when no power
is applied. For Failsafe operation the NO contacts are closed under nonalarm conditions. The NC contacts
close upon alarm and upon loss of power. The terms Setpoint 1 and Setpoint 2 refer to dual-trip alarms. For
single-trip alarms, both sets of contacts respond to the one trip point.
DETAILED SPECIFICATIONS
| Input Capabilities: |
Any input span 4mV or higher. Offset ranges are allowed. |
| Input Thermocouple Type: |
Any standard thermocouple type (J, K, T, E, R, S, B, N). Others
possible – contact factory. |
| Thermocouple Burnout Indication: |
Jumper-selectable upscale (offscale high) or downscale (offscale
low). Factory set for upscale unless otherwise specified. |
| Relay Contacts: |
Single Alarm, one DPDT relay. Dual Alarm, two SPDT relays. Contacts
rated 5 Amps resistive, 115/230Vac or 30Vdc. 1/8 HP max inductive load at 115/230Vac. Refer to instructions
for contact protection when switching inductive loads. |
| Setpoint Adjustment: |
0% to 100% of range. |
| Deadband Adjustment: |
0.25% to 100% of range. |
| Response Time: |
under 100 milliseconds. |
| Isolation: |
Input is isolated from power and from relay contacts. 1,500Vac rms
(2,100V peak) breakdown. |
| Guaranteed Operating Temperature: |
-10 to +60 deg. C (14 to 140 deg. F). |
| Temperature Stability: |
+/-(0.02% of span plus 1.3 microvolts) per deg. C, or better. |
| Power Requirements: |
AC, 115 or 230Vrms, 50/60 Hz., 2.5V-A. DC, 12 or 24Vdc, 2.5W. |
|