MODEL JH225: 2-WIRE TRANSMITTER
THERMOCOUPLE INPUT, USER-RANGEABLE, NONISOLATED

- Thermocouple Types J, K and
T
- Input Ranges as Low as 2mV
- Low-Drift Input Amplifier
- Fits Standard Connection Heads
- -40 to +80 Degree C Operation
|
JH225
PDF
FILE |
The Model JH225 2-wire transmitter provides a 4/20mA current loop output proportional to
the input from a thermocouple. 16-position Zero and Span switches plus fine-adjust trimpots allow
recalibration over a wide range of gains and offsets. Types J, K or T thermocouples may be selected. Cold
junction compensation is located in the terminal block for optimum accuracy. Conformal coating protects the
circuitry against condensation and corrosion in industrial atmospheres. Upscale burnout indication is
standard.
The JH225 is a loop-powered device. Connected in series between a 24Vdc supply and readout
instruments, it receives its power from the 4/20mA output loop. A built-in LED indicates loop current: dim at
4mA, bright at 20. The JH225 does not provide input/output isolation.
For a fixed range, factory-calibrated 2-wire thermocouple transmitter capable of handling
all standard thermocouple types see Model JH220.
ORDERING INFORMATION
| Model Number: |
Model JH225.
|
| Input Range: |
The JH225 is normally shipped tested but
uncalibrated. If you would like us to calibrate it simply specify on your order. We’ll do so at no extra
charge. Specify thermocouple type J, K or T and specify any input range allowed by the "Input
Capabilities" spec, below.
|
|
T/C Burnout Indication: |
(Always upscale – offscale high.)
|
| Output Range: |
(Always 4/20mAdc.)
|
| Power: |
(Always dc loop powered.)
|
|
DIN-Rail Mounting: |
Change model number to Model JH225-DIN. (See
"Installation and Connections," below.)
|
INSTALLATION AND CONNECTIONS
The JH225 is 1-3/4 inches in diameter and is designed to fit many standard
thermocouple-type connection heads. It may also be mounted to any surface using two #8 (or smaller) screws.
An optional DIN-rail mounting clip (specify Model JH225-DIN) allows the transmitter to be snapped onto DIN
rail. Width is 1-3/4 inches.
Connections are made to the transmitter’s terminal strip. Connections are:
"+" Terminal: Output/Power Loop. Receives current from
(+) DC supply.
"-" Terminal: Output/Power Loop. Passes on current to the next series loop
device, or to the (-) supply.
Terminal A: Thermocouple plus.
Terminal B: No connection –
compensator is encapsulated in this position.
Terminal C: Thermocouple minus. (On most thermocouples,
the red wire is minus.)
DETAILED SPECIFICATIONS
|
Input Capabilities: |
Span may be set anywhere from 2mV to 60mV.
Low end (zero) may be set as follows: Type J, -210 to +340 deg. C. Type K, -270 to +520 deg. C. Type T, -270
to +400 deg. C.
|
|
Input Thermocouple Types: |
May be set for use with types J, K or
T.
|
|
Thermocouple Burnout Indication: |
Output goes offscale high (above
20mA).
|
|
Output: |
4/20mA, 2-wire (loop-powered) output.
|
|
Accuracy (if properly calibrated): |
+/-0.1% of span or 10 microvolts, whichever is greater.
|
| Adjustability: |
Sufficient to achieve all specified input ranges.
|
| Linearity: |
Linear with millivolts. Does not linearize the
thermocouple.
|
| Response Time: |
Under 100 milliseconds.
|
| Guaranteed Operating Temperature: |
-40 to +80 deg. C (-40 to +176
deg. F).
|
| Temperature Stability: |
+/-(0.02% of span plus 1 microvolt) per
deg. C, or better.
|
| Power Requirements: |
DC loop-powered. Requires at least 12Vdc at
the transmitter’s output terminals. 36Vdc maximum.
|